dialog screen. Selecting the target CFG file and then selecting "Open" converts the file and
saves the resulting CSV file in the target file directory.
3.4.4
Clearing data log records from the HMI
1.
Press the Down Arrow (CNFG Hot Button) pushbutton to awaken the unit. The
menu will advance to "CONFIGURATION".
2.
Press the Down Arrow pushbutton once. The unit will display the following:
Tapchanger Type
3.
Press the Right or Left arrow pushbutton, as necessary, to navigate to the "Data
Logging" menu.
4.
Press the Down arrow pushbutton, as necessary, until the "Press ENT to clear Data
Log Records" screen is displayed.
5.
Press the ENT pushbutton. If prompted, enter a valid Level 2 Access Code. The
following will be displayed:
Press ENT to confirm clearing Data Log
6.
Press the ENT pushbutton, the following sequence of screens will be displayed.
Erasing Data Log records...
Data Log records have been cleared.
3.5
Active setpoint profile
3.5.1
Setting active setpoint profile from TCC600
1.
Start TCC600®, then establish communications with the target control.
2.
Select
Setup/Profile/Set Active Profile
from the TCC600 toolbar.
Section 3
1VAC388793-MB A
Operation
54
TCC300
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......