GUID-F30E8D82-95A5-4460-AAEE-BBCD9FAD3FEB V1 EN
Figure 270:
Setpoints Successfully Written To The Control Dialog Screen
6.2.4
Inputs and switch configuration
6.2.4.1
Setting Input Selection 1 Operation Counter Input Configuration to Switch
Status from the HMI
1.
Press the Down Arrow (CNFG Hot Button) pushbutton to wake the unit. The menu
will advance to "CONFIGURATION".
2.
Press the Down Arrow pushbutton once. The unit will display the following:
Tapchanger Type
3.
Press the Right or Left Arrow pushbutton, as necessary, until "Input Selection" is
displayed.
4.
Press the Down arrow pushbutton, as necessary, until the "Input Selection 1" screen
is displayed.
5.
Press the ENT pushbutton. If prompted, enter a valid Level 2 Access
Input Selection 1
SWITCH STATUS C
Input Selection 1 is required to be set to "Switch Status" if "Contact
KeepTrack™ 1R1L" or "Contact KeepTrack 1N" is selected for Tap
Information. The unit will display the following error message if
applicable:
Tap Info conflict
Any Key to Continue
6.
Utilizing the Up/Down arrow pushbuttons, select "SWITCH STATUS" then press
the ENT pushbutton.
The applicable counter type must be selected in Tap Settings.
1VAC388793-MB A
Section 6
Configuration
TCC300
345
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......