
6.2.5.2
Setting Input Selection 1 Operation Counter Input Configuration to Motor
Seal-In from TCC600
If Tap Information is selected to either "Contact KeepTrack 1R1L" or
"Contact KeepTrack 1N" the control will not accept an Input Selection 1
setting of "Seal-In Input". TCC600 will display the Tap Information/Input
Selection Error Screen if applicable.
GUID-B6D4D46A-325E-40E8-98DC-360F2D08C41C V1 EN
Figure 275:
Tap Information/Input Selection Conflict Error Screen
1.
Select
Setup/Configuration
from the TCC600 toolbar. TCC600 will display the
Tap Configuration dialog screen.
1VAC388793-MB A
Section 6
Configuration
TCC300
351
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......