Input Selection 1 must be set to "Switch Status" if Tap Position
Knowledge is to be selected to either "Contact KeepTrack
TM
1R1L" or
"Contact KeepTrack 1N".
Inputs and Switch
Input Selection 1
Switch Status
[Switch Status]
Seal-In Input
Input Selection 2
Non-sequential
[Non-sequential]
SCADA Cutout
Input Selection 3
VR2 [VR2]
Aux
Auto/Man Switch Type
None [None]
Toggle
SCAMP
Regulator
Type A [Type A]
Type B
Remote Voltage Bias (RVB)
Disable [Disable]
Enable
RVB Scale Factor
0.1 to 100.0 [1.0]
(_______________)
RVB Heartbeat Timer
2 to 120 (sec) [5]
(_______________)
Reverse RVB Scale Factor
0.1 to 100.0 [1.0]
(_______________)
Run Through Neutral (RTN)
Disable [Disable]
Enable
Maximum Allowed Taps
3 to 7 [4]
(_______________)
Tap Operations Between Runs
10 to 10000 [1000]
(_______________)
Maximum Load Current
1 to 200 (mA) [50]
(_______________)
Max RTN Standby Operations
1 to 10000 [20]
(_______________)
Fast Voltage Recovery
Disable [Disable]
Enable
Fast Voltage Recovery
1.0 to 15.0 (V) [5.0]
(_______________)
1VAC388793-MB A
Section 11
Appendix B Setpoint, Configuration and Communication Record Forms
TCC300
659
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......