Source VT Correction
0.0 Volts
VT ratio correction is adjustable from –15 V to +15 V in 0.1 V increments with a factory
setting of 0 V.
Norm. VT. Multiplier
1.00
Normalizing Voltage Multiplier 0.80 to 1.20 times the Compensating Voltage.
Power Display Option
SINGLE_PHASE
Toggles between two modes of operation: Single
‑
Phase – based on measured inputs, and
Three
‑
Phase – based on measured inputs and presumed balanced system. Factory setting
is single-phase.
Regulator Type
TYPE A
Allows the regulator type to be selected as Type A or B for correct source voltage
calculation. Factory setting is Type A.
Output Selection
CONTINUOUS
Allows choice of output at tapchanger Raise/Lower output terminal. Choices are
continuous or pulsed. For continuous, the control must wait to be in band or counter input
valid for output to become disabled. For pulsed, an adjustable pulse width will be applied
to the output triacs of 0.2 to 12 seconds.
Output Pulse
1.5 Sec
Adjustable from 0.2 to 12 seconds in 0.1 second increments. Factory set at 1.5 seconds.
Low Current Block
disable
Section 10
1VAC388793-MB A
Appendix A HMI
638
TCC300
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......