6.2.1.2
Setting programmable alarm relay inputs from the HMI
Each alarm condition corresponds to one of the digits on the bottom line of the display: a
"0" indicates that the alarm condition is disabled; a "1" indicates that the alarm condition
is enabled.
1.
Press the Down Arrow (CNFG Hot Button) pushbutton to wake the unit. The menu
will advance to "CONFIGURATION".
2.
Press the Down Arrow pushbutton once. The unit will display the following:
Tapchanger Type
3.
Press the Right or Left arrow pushbutton, as necessary, to navigate to the
"Programmable Alarm" menu.
4.
Press the Down arrow, as necessary, until either of the following are displayed
depending upon whether the Auto/Manual Switch Type is selected to "SCAMP".
Prog Alarm Function
–<0000000000000000
OR when the Auto/Manual Switch Type is selected to "SCAMP":
Prog Alarm Function
NORMAL or AS DEADMAN OUT
5.
If the unit displays the Programmable Alarm setup screen (zeros and/or ones on Line
2), then proceed to Step 8.
6.
If the unit displays the "SCAMP" Programmable Alarm Function screen, an
additional step is required to access the Programmable Alarm setup screen. Press the
"ENT" pushbutton. If prompted, enter a valid Level 2 Access Code.
7.
Ensure the selection is set to "NORMAL" and press the "ENT" pushbutton.
8.
Press the ENT pushbutton. The following will be displayed:
communication block
–<0000000000000000 C
See
for the index of alarm functions.
9.
Utilizing the arrow pushbuttons, enter a "1" for those Alarm Functions to be
activated and a "0" for those that are to be disabled, then press the ENT pushbutton.
The selected alarm will change from "lower case" when disabled (0), to "UPPER
CASE" when activated (1).
6.2.1.3
Programmable alarm relay mode
When the Auto/Man Switch Type is set to "SCAMP", the Programmable Alarm Function
can be set to "Normal" or "As a Deadman Output". This option is used since the Deadman
Output is not available. The default configuration setting is NORMAL.
Section 6
1VAC388793-MB A
Configuration
330
TCC300
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......