Table 9:
Communication menu contents
Item
Description
Disconnect
The Disconnect menu item when selected prompts the user to confirm
).
Open Terminal Window
Not Available at this time.
Setup
Comm Port
The Comm Port settings can be modified in the Setup Comm Port
) when the RS-485/Fiber Optic rear Comm Port is
present.
RS-232 Comm Port
The RS-232 Comm Port settings can be modified in the Setup RS232
Comm Port dialog (
) when the RS-232 Comm Port is present.
Ethernet
The Ethernet Port Settings can be modified in the Setup Ethernet dialog
(
) when the Ethernet Port is present.
Change Address
Multiple Control Addressing
The Control Communication Address can be modified in the Change
Communication Address screen (
Address is used for both MODBUS® and DNP protocols. Substation
and Feeder Addresses apply only to DNP protocol.
When Change Address submenu item is selected, TCC600® will
respond with a confirming dialog screen (
), As long as
communication to the remote location is maintained, the user can
switch between controls.
Miscellaneous:
Save – The Save command saves the Address change to the control
when TCC600 is connected to a control.
Close – The Close command cancels any Address changes before the
changes have been sent to the control.
Communication Access Security
When Communication Access Security is enabled it applies only when
MODBUS has been selected regardless of the physical interface. If
enabled, the user Level Access Code must match either the Level 1 or
Level 2 Access Codes in order to be granted the access to control
settings ascribed to each Level. If an invalid Access Level Code is
entered at the connection prompt, then read only access will be
granted. TCC600® must be closed for the timeout period specified (1 to
50,000 seconds) in order for any Access Code changes to take effect
when this feature is enabled. The setting range is from 1 to 50,000
seconds (
).
HeartBeat Option
The purpose of the SCADA HeartBeat feature is to have two sets of
settings for the control and switch between these two setting sets
based on the presence or absence of SCADA communications
(utilizing the DNP protocol) to the control. The SCADA HeartBeat
feature can be enabled from TCC600 Communications software. There
are four different types of SCADA HeartBeat modes that can be
selected:
•
SCADA HeartBeat for transformer control applications (LTC)
•
SCADA HeartBeat for regulator control applications (Regulator)
•
Profile Switching (DNP)
•
Profile Switching (GOOSE)
HeartBeat can be enabled or disabled (
) and the control type
selected.
Bluetooth
®
Settings
The Bluetooth Information dialog screen (
) provides the user
with the capability to setup Bluetooth communication parameters and
also initiate a "Reset" of the Bluetooth module.
Table continues on next page
1VAC388793-MB A
Section 4
TCC600
TCC300
145
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......