Figure 406:
Setpoints Successfully Written To The Control Confirmation
Screen
7.3.5
Save Voltage Reduction at power off
Save Voltage Reduction at Power Off allows the state of the "Voltage Reduction"
communication command to be saved or not saved when power has been lost. The default
setting is "DON'T SAVE".
7.3.5.1
Setting Save Voltage Reduction at Power Off from the HMI
1.
Press the Up Arrow (SETP Hot Button) pushbutton to wake the unit. The menu will
advance to "SETPOINTS".
2.
Press the Down Arrow pushbutton once. The unit will display the following:
Profile Settings
3.
Press the Right or Left Arrow pushbuttons as necessary until the following is
displayed:
Voltage Reduction
4.
Press the Down Arrow pushbutton as necessary to navigate to the "Save VR at Power
Off" menu item.
5.
Press the ENT pushbutton. If prompted, enter a valid Level Access Code. The
following will be displayed:
Save VR at Power Off
DON'T SAVE C
6.
Utilizing the Up/Down arrow pushbuttons, select "DON'T SAVE or SAVE", then
press the ENT pushbutton. The selected setting will be displayed.
7.3.5.2
Selecting Save Voltage Reduction at Power Off from TCC600
1.
Select
Setup/Setpoints
from the TCC600® toolbar. TCC600 will display the
Setpoints dialog screen.
1VAC388793-MB A
Section 7
Setpoints
TCC300
509
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......