
GUID-2EDBFD25-222B-4846-9AA2-CDFA5AE21B47 V1 EN
Figure 262:
Tap Settings Dialog Screen
2.
Select the desired Operation Counter configuration (X1, X2, Count Window or Cam
Follower).
3.
If "X1 or X2" configuration was selected in Step 2, enter the desired "X Mode Delay"
setting (0 to 3000 mS).
4.
If "Count Window" configuration was selected in Step 2, enter the desired "Count
Window" setting (0.5 to 60.5 seconds).
5.
Select
Save
. TCC600 will display a "Confirm Writing to Device" confirmation
screen.
GUID-64E3E9D7-7F66-4451-906E-B934BF7F9785 V1 EN
Figure 263:
Save to Device Confirmation Screen
6.
Select
OK
. TCC600 will display a "Setpoints Successfully Written to the Control"
confirmation screen.
Section 6
1VAC388793-MB A
Configuration
340
TCC300
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......