Figure 409:
Setpoints Successfully Written To The Control Confirmation
Screen
7.3.6
Setting Voltage Reduction Turnoff Timer from the HMI
1.
Press the Up Arrow (SETP Hot Button) pushbutton to wake the unit. The menu will
advance to "SETPOINTS".
2.
Press the Down Arrow pushbutton once. The unit will display the following:
Profile Settings
3.
Press the Right or Left Arrow pushbuttons as necessary until the following is
displayed:
Voltage Reduction
4.
Press the Down arrow pushbutton, as necessary, until the "Voltage Reduction
Turnoff Timer " screen is displayed.
5.
Press the ENT pushbutton. If prompted, enter a valid Level Access Code. The
following will be displayed:
VRed Turnoff Time
0 Min C
6.
Utilizing the arrow pushbuttons, select the desired Voltage Reduction Turnoff
Timer value (0 to 999 min), then press the ENT pushbutton.
7.3.7
Setting Voltage Reduction Turnoff Timer from TCC600
1.
Select
Setup/Setpoints
from the TCC600® toolbar. TCC600 will display the
Setpoints dialog screen.
1VAC388793-MB A
Section 7
Setpoints
TCC300
511
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......