Figure 288:
Save to Device Confirmation Screen
4.
Select
OK
. TCC600 will display a "Setpoints Successfully Written to the Control"
confirmation screen.
GUID-F30E8D82-95A5-4460-AAEE-BBCD9FAD3FEB V1 EN
Figure 289:
Setpoints Successfully Written To The Control Dialog Screen
6.2.7
Ratio multipliers
6.2.7.1
Voltage and current multipliers
The voltage and current multipliers do not affect the regulation of the
control. They are only used in the calculation of primary values.
The use of a voltage correction factor is incorporated in the calculation of
primary quantities in the control. Although the control operation is not
affected, erroneous values will be displayed and recorded if the VT
correction factor is not included in the PT multiplier.
Primary quantities are displayed when voltage and current multipliers are set in the
control. The voltage multiplier is:
V
mult
= V
pri
/(V
sec
+ V
corr
)
For a VT ratio of 7620/117 V and a voltage correction of 3 V, the multiplier is:
Section 6
1VAC388793-MB A
Configuration
360
TCC300
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......