1.
Press the Up Arrow (SETP Hot Button) pushbutton to wake the unit. The menu will
advance to "SETPOINTS".
2.
Press the Down Arrow pushbutton once. The unit will display the following:
Profile Settings
3.
Press the Down arrow pushbutton as necessary until the unit displays the following:
Edit Profile 1 name
0
4.
Press the ENT pushbutton. If prompted, enter a valid Level Access Code.
5.
Utilizing the arrow pushbuttons, enter the desired Setpoint Profile Name, then press
the ENT pushbutton. The following will be displayed reflecting the Setpoint Profile
Name that was entered.
Edit Profile 1 name
XXXXXXX
7.1.2.2
Assigning a setpoint profile name from TCC600
1.
Select Setup/Profile/Profile Names from the TCC600 toolbar. TCC600 will display
the Profile Names dialog screen.
GUID-7C752949-D815-41B9-BAEE-5FF10F6B4204 V1 EN
Figure 391:
Setpoint Profile Names Dialog Screen
2.
Enter the desired names for Setpoint Profiles 1 through 4.
3.
Select
Save
. TCC600 will display a "Save to Device" confirmation screen.
Section 7
1VAC388793-MB A
Setpoints
492
TCC300
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......