Editing Setpoints in the wrong Setpoint Profile can cause the control
to operate incorrectly.
2.
Select the desired Setpoint Profile, then from the "General" section of the Setpoints
dialog screen, select the desired type of Line Drop Compensation (R, X or Z).
3.
From the "Forward Power" section of the Setpoints dialog screen, enter the desired
LDC R, X or Z for Forward Power settings for the following:
•
R, X (–72 to +72 in 1 Volt increments)
•
Z (0 to 72 in 1 Volt increments)
If Re verse Power Flow settings are required, enter the desired LDC R, X or Z values
in the "Reverse Power" section of the Setpoints dialog screen.
Selecting "Save" saves all profiles to the control.
4.
Select
Save
. TCC600 will display a "Confirm Writing to Device" confirmation
screen.
GUID-64E3E9D7-7F66-4451-906E-B934BF7F9785 V1 EN
Figure 414:
Save to Device Confirmation Screen
5.
Select
OK
. TCC600 will display a "Setpoints Successfully Written to Control"
confirmation screen.
GUID-F30E8D82-95A5-4460-AAEE-BBCD9FAD3FEB V1 EN
Figure 415:
Setpoints Successfully Written To The Control Confirmation
Screen
Section 7
1VAC388793-MB A
Setpoints
520
TCC300
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......