4.10.5.12
CBEMA Events
Setup
There are a total of 4 Event Monitors in CBEMA (Computer Business Equipment
Manufacturers Association). Each CBEMA event monitor has a different minimum
duration limit; Event 1, 1 – 60 cycles, Event 2, 1 – 120 cycles, Event 3, 60 – 60000 cycles
and Event 4, 1 – 60 cycles. When Pickup is set to less than 100% it operates as a sag (under
voltage) function, and when it is greater than 100% it operates as a swell (over voltage)
function.
GUID-B2EEC973-DB34-457C-B220-832923151E0D V1 EN
Figure 145:
CBEMA Setting Dialog Screen