GUID-64E3E9D7-7F66-4451-906E-B934BF7F9785 V1 EN
Figure 335:
Save to Device Confirmation Screen
4.
Select
OK
. TCC600 will display a "Setpoints Successfully Written to the Control"
confirmation screen.
GUID-F30E8D82-95A5-4460-AAEE-BBCD9FAD3FEB V1 EN
Figure 336:
Setpoints Successfully Written To The Control Dialog Screen
6.3.2
Optional master/follower parallelling method
The Master/Follower Paralleling scheme employs the GOOSE messaging of the IEC
61850 protocol to provide peer to peer communications. The control can be placed in
either the Master or Follower mode if paralleling is to be achieved. The Master/Follower
settings can also be changed individually on each control through Setup/Configuration/
Paralleling. The Master/Follower Configuration Tool includes the settings for each
control in the network for the Master/Follower paralleling scheme.