GUID-217CAB51-2F4A-4235-B7F3-4985B331F3EC V1 EN
Figure 53:
Remote Control Screen for SCAMP Auto/Manual Switch Type
Remote Control allows the user to:
•
Remotely raise or lower one tap position.
•
Apply Voltage Reduction Step 1 or 2 or 3.
•
When the Auto/Manual Switch Type is set to either "Toggle" or "NONE" the Block
Auto Control via Communication (Comm Block) setting is available.
•
When the Auto/Manual Switch Type is set to "SCAMP" the SCAMP Auto/Manual
Control setting is available.
Remote Tap Control
If the unit is supplied with DC Power Backup, then all automatic Raise or
Lower operations are blocked when the input voltage decreases to less
than 85.0 Vdc. Remote initiated Raise or Lower operations will still be
initiated if Motor Power is available.
The control will not accept a new command unless the previous command
is completed.
Lower 1 Tap
Section 3
1VAC388793-MB A
Operation
110
TCC300
User Manual