GUID-64E3E9D7-7F66-4451-906E-B934BF7F9785 V1 EN
Figure 411:
Save to Device Confirmation Screen
4.
Select
OK
. TCC600 will display a "Setpoints Successfully Written to Control"
confirmation screen.
GUID-F30E8D82-95A5-4460-AAEE-BBCD9FAD3FEB V1 EN
Figure 412:
Setpoints Successfully Written To The Control Confirmation
Screen
7.4
Line drop compensation
Voltage Regulation Without LDC
When the control is just used to regulate the voltage on the regulator low-side bus, the only
input required is voltage from a line-to-line or line-to-ground VT with a nominal 120 Vac
secondary.
Voltage Regulation With LDC
When it is desirable to regulate the voltage at some distance from the voltage regulator, or
in general to raise the voltage during high load conditions, the Line Drop Compensation
(LDC) feature is used.
Two different LDC methods are available in the TCC300 Digital Tapchanger Control. A
selection in the Setpoints/General section allows the user to select from either Resistance/
Reactance (R/X) or LDC-Z.
1VAC388793-MB A
Section 7
Setpoints
TCC300
513
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......