GUID-F30E8D82-95A5-4460-AAEE-BBCD9FAD3FEB V1 EN
Figure 258:
Setpoints Successfully Written To The Control Dialog Screen
6.2.2
Op Count Signal Alarm
The Op Count Signal Alarm feature provides the user with the ability to set a predefined
alarm point for the number of tapchanges initiated by the control. When the predefined
alarm setting is exceeded, the following alarm message will be displayed on the HMI
screen:
Op Count Signal Alarm
Rst Op Count XXX
6.2.2.1
Setting Op Count Signal Alarm from the HMI
1.
Press the Down Arrow (CNFG Hot Button) pushbutton to wake the unit. The menu
will advance to "CONFIGURATION".
2.
Press the Down Arrow pushbutton once. The unit will display the following:
Tapchanger Type
3.
Press the Right or Left arrow pushbutton, as necessary, until "Programmable Alarm"
is displayed.
4.
Press the Down arrow, as necessary, until the following is displayed.
Op Count Signal Alrm
0
5.
Press the ENT pushbutton. If prompted, enter a valid Level 2 Access Code.
6.
Utilizing the Up/Down arrow pushbuttons enter the desired alarm value, then press
the ENT pushbutton.
6.2.2.2
Setting Op Count Signal Alarm from TCC600
1.
Select
Setup/Tap Settings
from the TCC600 toolbar. TCC600 will display the Tap
Settings dialog screen.
1VAC388793-MB A
Section 6
Configuration
TCC300
333
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......