4.10.5.8
Data Logging
Data is recorded internally into non volatile memory. The data log is transferred in the
Comtrade format. The Comtrade format consist of two files, the configuration file (*.cfg)
and the data file (*.dat).
Data logging will continue indefinitely as long as the data interval is set to a non-zero
value. A zero value for the data interval will effectively disable data logging. The data log,
can be downloaded using MODBUS® (see TCC300 protocol document) or DNP (using
file transfer) protocol. The data can be viewed using any Comtrade compatible viewer.
TCC600 provides such a tool.
Data logging interval ranges from 0 to 120 min with an increment of 1 minute. Once data
logging is enabled, the control will store the data in records at the data interval rate. Each
record has the following data:
•
Load Voltage
•
Primary VA
•
Power Factor
•
Source Voltage
•
Compensated Voltage
•
Primary VAr
•
Frequency
•
Primary Watts
•
Load Current
•
Tap Position
•
Primary Current
•
Operations Count
•
Circulating/DVAr Current
•
Meter Out Voltage
•
RTN Counter
The checksum is used to ensure the integrity of the record stored. The average value is
calculated over the data logging interval.
Due to the internal structure of the Comtrade format, time stamping is always performed.
A total of 6 Mbytes (100,000 records) of data can be saved in non volatile memory.
When connected to a TCC300 Tapchanger Control the Data Logging feature provides the
user with the ability to initiate data logging of all control parameters to the selected control
for downloading at a later time.
This feature allows the user to configure the parameters that the control will use to log
data, and to download the logged data to a Comtrade (*.cfg) file. This file format can be
viewed by a third party Common Format for Transient Data Exchange (COMTRADE)
format viewer software.
1VAC388793-MB A
Section 4
TCC600
TCC300
201
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......