Don’t Save – Allows the state of the "Block Auto Operation" communication
command to NOT be saved when power has been lost.
•
Save – Allows the state of the "Block Auto Operation" communication command to
be saved when power has been lost.
SCAMP Initialize on Power Up
When the Auto/Manual Switch Type is set to "SCAMP", the following selections are
available:
When Last Save is selected, the SCAMP switch is configured in such a way that upon the
control performing a cold power up, the state of the SCAMP switch is initialized to the last
saved state of the SCAMP switch prior to the control powering off.
For example, if prior to powering off the control, the SCAMP switch was in Manual, then
when the control is powered back on the control will initially go back to the Manual state
and vise versa. Now when Auto Mode is selected, the control always initializes into the
Auto Mode after powering up regardless of the saved state of the control prior to powering
off.
Table 40:
Fast Voltage Recovery
Item
Description
Enable/Disable
Allows Fast Voltage Recovery to be Enabled or
Disabled.
Fast Voltage Recovery
Allows a setting from 1.0 to 15.0 V outside the normal
band edges in 1.0 V increments. When voltage
exceeds the Raise or Lower band edge plus the Fast
Voltage Recovery setting, the normal definite or
inverse time delay is replaced with instantaneous
operation (<0.5 Sec).
Table 41:
Miscellaneous
Item
Description
Undo/Refresh
The Undo command allows the user to undo any
setting changes in the Configuration screen before
the settings have been saved to either the Device or
Open File. It also refreshes the screen with the data
stored in the unit.
Save
The Save command saves the setting changes to
either the Open File when in File mode or the Device
when TCC600® is connected to a device.
Close
The Close command cancels any hardware setting
changes before the hardware settings changes have
been sent to either the Device or Open File.
Section 4
1VAC388793-MB A
TCC600
192
TCC300
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......