GUID-64E3E9D7-7F66-4451-906E-B934BF7F9785 V1 EN
Figure 378:
Save to Device Confirmation Screen
5.
Select
OK
. TCC600 will display a "Setpoints Successfully Written to the Control"
confirmation screen.
GUID-F30E8D82-95A5-4460-AAEE-BBCD9FAD3FEB V1 EN
Figure 379:
Setpoints Successfully Written To The Control Dialog Screen
6.5
Data logging and harmonics
6.5.1
Data logging
Whenever the TCC300 clock is reset and data logging is enabled, the data
log should be cleared.
The Data Logging feature allows the user to record data internally into non volatile
memory. The data log is transferred in the Comtrade format. The Comtrade format
consists of two files, the configuration file (*.cfg) and the data file (*.dat).
Data logging will continue indefinitely as long as the data Interval is set to a non-zero
value. A zero value for the data interval will effectively disable data logging. The data log
can be downloaded using MODBUS® (see TCC300 Protocol document) or DNP (using
file transfer) protocol. The data can be viewed using any Comtrade compatible viewer.
Section 6
1VAC388793-MB A
Configuration
476
TCC300
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......