Rev Max Cap Bank Size
12000 KVAr
Sets the largest capacitor bank size in the reverse mode from 4 to 12,000 KVAr.
Lead % Pickup
75
Defines a Lower negative VAr limit in percentage of the Max Cap Bank size below which
the control will increase the upper band edge by the amount defined by VAr Bias Voltage
Step.
Lag % Pickup
75
Defines an Upper positive VAr limit in percentage of the Max Cap Bank size above which
the control will decrease the lower band edge by the amount defined by VAr Bias Voltage
Step.
VAr Bias Volt Step
1.0 Volts
Amount by which the control will increase or decrease the Upper or Lower band edges
when there is a VAr Bias out of band situation.
Max VAR Bias Time
300 mins
Maximum allowable time in minutes the control will bias the voltage edge.
10.2.3.2
VAr Bias (Linear)
Disable on Rev Pwr
disable
Allows Linear VAr Bias to be disabled in the reverse power mode.
Curr Mult Base Value
0
Allows the Current Multiplier Base Value to be set between 0 and 32600.
Section 10
1VAC388793-MB A
Appendix A HMI
620
TCC300
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......