TAP = Tap Position
•
TAP Number = The number of tapchanges and the Accumulated Primary Current for
each individual tap position on the Tapchanger control.
Press ENT to clear
Tap Statistics
Press ENT to confirm clearing tap statistics.
RTN Success Counter
xxxxx
The RTN counter increments after each successful operation of the Run Through Neutral
feature.
RTN Status
Disabled/Enabled
Displays the status of the Run Through Neutral Feature.
Count to RTN Active
xxxxx
Displays the number of counter operations since the operations between runs setting was
set, or since the feature was enabled. The counter will reset to zero if the feature is enabled
and successfully runs through neutral.
10.2.2
Setpoints
10.2.2.1
Profile Settings
Active Profile
Profile: 1
Selects the Active Profile (1, 2, 3 or 4).
Profile to Edit
Profile: 1
Selects the Setpoint Profile to be edited (1, 2, 3 or 4).
Edit Profile 1 Name (2,3 or 4)
1VAC388793-MB A
Section 10
Appendix A HMI
TCC300
613
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......