7.3.4
Smart Voltage Reduction
Smart Voltage Reduction, when enabled, will lower voltage to between the new
Bandcenter setting and the lower band edge instead of stopping at the upper band edge. It
will also disable VAr Bias if it is in effect.
7.3.4.1
Enabling or disabling and setting Smart Voltage Reduction from the HMI
1.
Press the Up Arrow (SETP Hot Button) pushbutton to wake the unit. The menu will
advance to "SETPOINTS".
2.
Press the Down Arrow pushbutton once. The unit will display the following:
Profile Settings
3.
Press the Right or Left Arrow pushbuttons as necessary until the following is
displayed:
Voltage Reduction
4.
Press the Down Arrow pushbutton as necessary to navigate to the "Smart Voltage
Reduction" menu item.
5.
Press the ENT pushbutton. If prompted, enter a valid Level Access Code. The
following will be displayed:
Smart VR
disable C
6.
Utilizing the Up/Down arrow pushbuttons, select either "ENABLE" or Disable",
then press the ENT pushbutton.
7.3.4.2
Enabling or disabling and setting Standard or Smart Voltage Reduction
from TCC600
1.
Select
Setup/Setpoints
from the TCC600® toolbar. TCC600 will display the
Setpoints dialog screen.
1VAC388793-MB A
Section 7
Setpoints
TCC300
507
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......