the waveform data can be examined and printed using the TapPlot® Oscillograph Data
Analysis Software.
GUID-A53F1F0A-2EDF-4A7B-BE1D-3B5393FE92C7 V1 EN
Figure 133:
Oscillograph Setup Dialog Screen
The general information required to setup the Oscillograph Recorder includes:
•
Number of Partitions – When untriggered, the recorder continuously records
waveform data, keeping the data in a buffer memory. The recorder’s memory may be
partitioned into 1 to 16 partitions. When tr iggered, the time stamp is recorded and the
recorder continues recording for a user-defined period. The snapshot of the waveform
is stored in memory for later retrieval using TCC600 Communications Software.
•
Samples/Cycle – The number of samples/cycle can be selected to either 16, 32 or 64
samples/cycle.
•
Post-Trigger Delay – A post-trigger delay of 5% to 95% must be specified. After
triggering, the recorder will continue to store data for the programmed portion of the
total record before rearming for the next record. For example, a setting of 80% will
result in a record with 20% pre-trigger data and 80% post-trigger data.
1VAC388793-MB A
Section 4
TCC600
TCC300
205
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......