60000 ms C
20. Utilizing the arrow pushbuttons, enter the desired Tap Position Response Timeout
then press the ENT pushbutton.
21. Press the Down arrow pushbutton once, the "Breaker Option" screen will be
displayed.
22. Press the ENT pushbutton. If Level 2 Access is not active or has been previously
input, the following will be displayed.
line breaker
000000 C
23. Utilizing the arrow pushbuttons, enter the desired Breaker Options:
Position 1 is the first position from the right.
Position 1 – Line Breaker (A1)
•
"0" = Not Selected
•
"1" = Selected
Position 2 – Line Breaker Polarity
•
"0" = Positive
•
""1" = Negative
Position 3 – Right Tie Breaker (A2)
•
"0" = Not Selected
•
"1" = Selected
Position 4 – Right Tie Breaker Polarity
•
"0" = Positive
•
""1" = Negative
Position 5 – Left Tie Breaker (A3)
•
"0" = Not Selected
•
"1" = Selected
Position 6 – Left Tie Breaker Polarity
•
"0" = Positive
•
""1" = Negative
When all Break er Options have been entered, then press the ENT pushbutton.
24. Press the Down arrow pushbutton once, the "Tap Difference" screen will be
displayed.
The Tap Difference setting is the difference between Master and Follower tap
positions for which Lockout will be issued.
1VAC388793-MB A
Section 6
Configuration
TCC300
427
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......