occurrence. If a Motor Seal-in Failure is detected in the opposite direction, then operation
will be blocked in that direction also.
This Block can be reset by the user from the HMI, from the TCC600 "Alarms" dialog
screen or via SCADA. The block is also reset when a successful tapchange operation
occurs (motor seal-in current is detected) in the opposite direction.
The internal accumulator that counts the occurrences of failed tapchanges is stored in
volatile memory and is set to zero when a loss of power occurs and the unit is not equipped
with a backup power supply. This is considered normal operation of the feature.
6.2.5.1
Setting Input Selection 1 Operation Counter Input Configuration to Motor
Seal-In from the HMI
If Tap Information is selected to either "Contact KeepTrack™ 1R1L" or
"Contact KeepTrack 1N" the control will not accept an Input Selection 1
setting of "Seal-In Input". The unit will display the following error
message if applicable:
Tap Info conflict
Any Key to Continue
Motor Seal-in Delay is fixed at 3 seconds.
1.
Press the Down Arrow (CNFG Hot Button) pushbutton to wake the unit. The menu
will advance to "CONFIGURATION".
2.
Press the Down Arrow pushbutton once. The unit will display the following:
Tapchanger Type
3.
Press the Right/Left arrow pushbutton as necessary to navigate the "Input Selection"
screen.
4.
Press the Down arrow pushbutton, as necessary, until the "Input Selection 1" screen
is displayed.
5.
Press the ENT pushbutton. If prompted, enter a valid Level 2 Access Code. The
following will be displayed:
Input Selection 1
SWITCH STATUS C
6.
Utilizing the Up/Down arrow pushbuttons, select "SEAL-IN INPUT", then press the
ENT pushbutton.
Section 6
1VAC388793-MB A
Configuration
350
TCC300
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......