Figure 368:
Tap Settings Dialog Screen
2.
Verify that a "Regulate (Reg or XFMR) External" mode is selected in the "General"
section of the dialog screen.
In order to verify Neutral Tap Position, when the tap position is "0",
but no neutral input is detected, the Tap Position screen of the
TCC300 will display "- - -" instead of "0". When reading the tap
position via comms (Modbus and DNP) a value of 32767 will be
returned when the tap position is "0", but no neutral input is detected,
otherwise a "0" will be returned.
3.
Determine and note the actual tap position from the external tap position indicator on
the regulator or transformer.
4.
Enter the tap position noted in Step 3, then select "Yes" for Tap Calibrate.
5.
Select
Save
. TCC600 will display a "Confirm Writing to Device" confirmation
screen.