Table 16:
INPUT STATUS
Item
Description
Neutral Tap
Indicates (Green) neutral position contact input is
closed.
Counter
Indicates (Green) operation counter contact input is
closed.
Non-Sequential
Indicates (Green) Non‑sequential contact input is
closed. Tapchanger control blocks raise or lower
operation on a sustained closed contact.
Motor Seal-in
Indicates (Green) when motor power is applied.
Volt Reduction 1
Indicates (Green) Step 1 voltage reduction contact
output is closed.
Volt Reduction 2
Indicates (Green) Step 2 voltage reduction contact
output is closed.
SCADA Cutout
Indicates (Green) SCADA (switch) input is closed.
Tapchanger control blocks Raise or Lower
operation.
Table 17:
OUTPUT STATUS
Item
Description
Raise
Indicates (Green) when a Tap Raise output is active.
Limited by tap Block Raise setpoint and tap position
limit settings.
Lower
Indicates (Green) when a Tap Lower output is active.
Limited by tap Block Lower setpoint and tap position
limit settings.
Programmable Alarm
Indicates (Green) when a Programmable Alarm
condition is true.
Motor Seal-In
Indicates when a Motor Seal-In Output in active.
CBEMA EVENTS AND COUNTER STATUS
When the Load Voltage is sagging or swelling greater than the pickup setting, then a
pickup status will be set after a minimum duration, in addition to incrementing a counter.
Up to 4 CBEMA events can be set and enabled allowing the control to trigger a Sequence
of Events record when each event occurs. Also, the control will report both the time and
duration of each event via DNP. These 4 settings allow the control to be set to record
violations of the ITIC curves (formerly known as CBEMA curves).
AUX INPUT STATUS
Indicates (red) when the Auxiliary Input is active.
Section 4
1VAC388793-MB A
TCC600
160
TCC300
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......