Table 36: Test mode
Test mode
Description
Protection BEH_BLK
Normal mode
Normal operation
FALSE
IED blocked
Protection working as in “Normal mode” but
ACT configuration can be used to block phys-
ical outputs to process. Control function
commands blocked.
TRUE
IED test
Protection working as in “Normal mode” but
protection functions are working in parallel
with test parameters.
FALSE
IED test and blocked
Protection working as in “Normal mode” but
protection functions are working in parallel
with test parameters. ACT configuration can
be used to block physical outputs to process.
Control function commands blocked.
TRUE
Behavior data objects in all logical nodes follow LD0.LLN0.Mod value. If
"Normal mode" is selected, behaviour data objects follow mode (.Mod)
data object of the corresponding logical device.
3.7.3
Application configuration and Test mode
The physical outputs from control commands to process are blocked with ”IED
blocked” and “IED test and blocked” modes. If physical outputs need to be blocked
from the protection, the application configuration must be used to block these
signals. Blocking scheme needs to use
BEH_BLK
output of PROTECTION function
block.
3.7.4
Control mode
The mode of all logical nodes located under CTRL logical device can be set with
Control mode. The Control mode parameter is available via the HMI or PCM600
path Configuration > Control > General. By default,
Control mode can only be set
locally through LHMI. To set the parameters from WHMI the
Remote test mode
parameter under Tests > IED test > Test mode should first be set to “All Levels”.
Control mode inherits its value from Test mode but Control mode ”On”, “Blocked”
and “Off” can also be set independently.
Control mode is also available via IEC 61850
communication (CTRL.LLN0.Mod).
Table 37: Control mode
Control mode
Description
Control BEH_BLK
On
Normal operation
FALSE
Blocked
Control function commands blocked
TRUE
Off
Control functions disabled
FALSE
Behavior data objects under CTRL logical device follow CTRL.LLN0.Mod
value. If "On" is selected, behavior data objects follow the mode of the
corresponding logical device.
1MRS757644 H
Basic functions
620 series
Technical Manual
95