Parameter
Values (Range)
Unit
Step
Default
Description
Zro V low low Lim
0.00...4.00
xUn
1
0.00
Low alarm voltage
limit for zero se-
quence voltage
Zro V deadband
100...100000
1
10000
Deadband configu-
ration value for
zero sequence volt-
age for integral cal-
culation. (percent-
age of difference
between min and
max as 0,001 % s)
8.1.11.5
Monitored data
Table 939: VSMSQI Monitored data
Name
Type
Values (Range)
Unit
Description
NgSeq-kV
FLOAT32
0.00...4.00
xUn
Measured nega-
tive sequence
voltage
PsSeq-kV
FLOAT32
0.00...4.00
xUn
Measured posi-
tive sequence
voltage
ZroSeq-kV
FLOAT32
0.00...4.00
xUn
Measured zero
sequence volt-
age
U2_INST
FLOAT32
0.00...4.00
xUn
Negative se-
quence voltage
amplitude, in-
stantaneous val-
ue
U2_ANGL
FLOAT32
-180.00...180.00
deg
Negative se-
quence voltage
angle
U2_DB
FLOAT32
0.00...4.00
xUn
Negative se-
quence voltage
amplitude, re-
ported value
U2_RANGE
Enum
0=normal
1=high
2=low
3=high-high
4=low-low
Negative se-
quence voltage
amplitude range
U1_INST
FLOAT32
0.00...4.00
xUn
Positive se-
quence voltage
amplitude, in-
stantaneous val-
ue
Table continues on the next page
1MRS757644 H
Measurement functions
620 series
Technical Manual