5.3.7
Settings
Table 785: TRPPTRC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Trip pulse time
20...60000
ms
1
250
Minimum duration
of trip output sig-
nal
Trip output mode
1=Non-latched
2=Latched
3=Lockout
1=Non-latched
Select the opera-
tion mode for trip
output
5.3.8
Monitored data
Table 786: TRPPTRC Monitored data
Name
Type
Values (Range)
Unit
Description
TRPPTRC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
5.3.9
Technical revision history
Table 787: TRPPTRC Technical revision history
Technical revision
Change
B
-
C
-
D
Internal improvement.
E
Setting
Trip output mode
default setting is
changed to "Latched".
F
Internal improvement.
5.4
High-impedance fault detection PHIZ
1MRS757644 H
Protection related functions
620 series
Technical Manual
819