Parameter
Values (Range)
Unit
Step
Default
Description
50=PFL1B
51=PFL2B
52=PFL3B
53=IL1C
54=IL2C
55=IL3C
Mem. warning level 0...100
%
1
0
Set memory warn-
ing level
Mem. alarm level
0...100
%
1
0
Set memory alarm
level
3.19.6
Monitored data
Table 210: LDPRLRC Monitored data
Name
Type
Values (Range)
Unit
Description
Rec. memory
used
INT32
0...100
%
How much re-
cording memory
is currently used
3.20
ETHERNET channel supervision function blocks
3.20.1
Redundant Ethernet channel supervision RCHLCCH
3.20.1.1
Function block
Figure 116: Function block
3.20.1.2
Functionality
Redundant Ethernet channel supervision RCHLCCH represents LAN A and LAN B
redundant Ethernet channels.
1MRS757644 H
Basic functions
620 series
Technical Manual
235