monitoring is not only an effective customer service strategy but also a way to
protect a utility's reputation for quality power and service.
CMHAI provides a method for monitoring the power quality by means of the current
waveform distortion. CMHAI provides a short-term 3-second average and a long-
term demand for TDD.
10.1.6
Signals
Table 1031: CMHAI Input signals
Name
Type
Default
Description
I_A
Signal
0
Phase A current
I_B
Signal
0
Phase B current
I_C
Signal
0
Phase C current
BLOCK
BOOLEAN
0=False
Block signal for all bi-
nary outputs
Table 1032: CMHAI Output signals
Name
Type
Description
ALARM
BOOLEAN
Alarm signal for TDD
10.1.7
Settings
Table 1033: CMHAI Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Demand interval
0=1 minute
1=5 minutes
2=10 minutes
3=15 minutes
4=30 minutes
5=60 minutes
6=180 minutes
2=10 minutes
Time interval for
demand calculation
Demand window
1=Sliding
2=Non-sliding
1=Sliding
Demand calculation
window type
TDD alarm limit
1.0...100.0
%
0.1
50.0
TDD alarm limit
Table 1034: CMHAI Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Initial Dmd current 0.10...1.00
xIn
0.01
1.00
Initial demand cur-
rent
Power quality measurement functions
1MRS757644 H
1084
620 series
Technical Manual