6.4.11
Technical revision history
Table 866: HZCCxSPVC Technical revision history
Technical revision
Change
B
Function name changed from HZCCRDIF to
HZCCASPVC, HZCCBSPVC, HZCCCSPVC.
6.5
Fuse failure supervision SEQSPVC
6.5.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE
C37.2 device
number
Fuse failure supervision
SEQSPVC
FUSEF
60
6.5.2
Function block
Figure 479: Function block
6.5.3
Functionality
The fuse failure supervision function SEQSPVC is used to block the voltage-
measuring functions when failure occurs in the secondary circuits between the
voltage transformer (or combi sensor or voltage sensor) and protection relay to
avoid misoperations of the voltage protection functions.
SEQSPVC has two algorithms, a negative sequence-based algorithm and a delta
current and delta voltage algorithm.
A criterion based on the delta current and the delta voltage measurements can
be activated to detect three-phase fuse failures which usually are more associated
with the voltage transformer switching during station operations.
Supervision functions
1MRS757644 H
898
620 series
Technical Manual