3.1.8
Binary input settings in card location Xnnn
Table 14: Binary input settings in card location Xnnn
Name
1
Value
Unit
Step
Default
Input m
2
filter time
5…1000
ms
5
Input m inversion
0= False
1= True
0=False
3.1.9
Ethernet front port settings
Table 15: Ethernet front port settings
Parameter
Values (Range)
Unit
Step
Default
Description
IP address
192.168.0.254
IP address for front
port (fixed)
Mac address
XX-XX-XX-XX-XX-XX Mac address for
front port
3.1.10
Ethernet rear port settings
Table 16: Ethernet rear port settings
Parameter
Values (Range)
Unit
Step
Default
Description
IP address
192.168.2.10
IP address for rear
port(s)
Subnet mask
255.255.255.0
Subnet mask for
rear port(s)
Default gateway
192.168.2.1
Default gateway
for rear port(s)
Mac address
XX-XX-XX-XX-XX-XX Mac address for
rear port(s)
1
Xnnn = Slot ID, for example, X100, X110, as applicable
2
m = For example, 1, 2, depending on the serial number of the binary input in a particular BIO card
Basic functions
1MRS757644 H
56
620 series