Parameter
Values (Range)
Unit
Step
Default
Description
A low low limit
0.00...40.00
xIn
1
0.00
Low alarm current
limit
A deadband
100...100000
1
2500
Deadband configu-
ration value for in-
tegral calculation.
(percentage of dif-
ference between
min and max as
0,001 % s)
Table 895: CMMXU Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Measurement
mode
1=RMS
2=DFT
2=DFT
Selects used meas-
urement mode
8.1.4.5
Monitored data
Table 896: CMMXU Monitored data
Name
Type
Values (Range)
Unit
Description
IL1-A
FLOAT32
0.00...40.00
xIn
Measured cur-
rent amplitude
phase A
IL2-A
FLOAT32
0.00...40.00
xIn
Measured cur-
rent amplitude
phase B
IL3-A
FLOAT32
0.00...40.00
xIn
Measured cur-
rent amplitude
phase C
Max demand IL1 FLOAT32
0.00...40.00
xIn
Maximum de-
mand for Phase
A
Max demand IL2 FLOAT32
0.00...40.00
xIn
Maximum de-
mand for Phase
B
Max demand IL3 FLOAT32
0.00...40.00
xIn
Maximum de-
mand for Phase
C
Min demand IL1
FLOAT32
0.00...40.00
xIn
Minimum de-
mand for Phase
A
Min demand IL2
FLOAT32
0.00...40.00
xIn
Minimum de-
mand for Phase
B
Min demand IL3
FLOAT32
0.00...40.00
xIn
Minimum de-
mand for Phase
C
Table continues on the next page
Measurement functions
1MRS757644 H
936
620 series