4.8.2.6
Signals
Table 700: DOPPDPR Input signals
Name
Type
Default
Description
I_A
SIGNAL
0
Phase A current
I_B
SIGNAL
0
Phase B current
I_C
SIGNAL
0
Phase C current
U_A_AB
SIGNAL
0
Phase-to-earth volt-
age A or phase-to-
phase voltage AB
U_A_BC
SIGNAL
0
Phase-to-earth volt-
age B or phase-to-
phase voltage BC
U_A_CA
SIGNAL
0
Phase-to-earth volt-
age C or phase-to-
phase voltage CA
BLOCK
BOOLEAN
0=False
Block signal for acti-
vating the blocking
mode
Table 701: DOPPDPR Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operate
START
BOOLEAN
Start
4.8.2.7
Settings
Table 702: DOPPDPR Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value
0.01...2.00
xSn
0.01
1.00
Start value
Operate delay time 40...300000
ms
10
40
Operate delay time
Directional mode
2=Forward
3=Reverse
2=Forward
Directional mode
Power angle
-90...90
deg
1
0
Adjustable angle
for power
Protection functions
1MRS757644 H
742
620 series