Name
Type
Description
AI_VAL3
FLOAT32
RTD input, Connectors
5-6-11c, instantaneous value
AI_VAL4
FLOAT32
RTD input, Connectors
7-8-11c, instantaneous value
AI_VAL5
FLOAT32
RTD input, Connectors
9-10-11c, instantaneous value
AI_VAL6
FLOAT32
RTD input, Connectors
13-14-12c, instantaneous val-
ue
AI_VAL7
FLOAT32
RTD input, Connectors
15-16-12c, instantaneous val-
ue
AI_VAL8
FLOAT32
RTD input, Connectors
17-18-12c, instantaneous val-
ue
Table 58: 2RTD/1mA analog output signals
Name
Type
Description
ALARM
BOOLEAN
General alarm
WARNING
BOOLEAN
General warning
AI_VAL1
FLOAT32
mA input, Connectors 1-2, in-
stantaneous value
AI_VAL2
FLOAT32
RTD input, Connectors 3-5, in-
stantaneous value
AI_VAL3
FLOAT32
RTD input, Connectors 6-8,
instantaneous value
3.13.4
RTD input settings
Table 59: RTD input settings
Parameter
Values (Range)
Unit
Step
Default
Description
Input mode
1=Not in use
2=Resistance
10=Pt100
11=Pt250
20=Ni100
21=Ni120
22=Ni250
30=Cu10
1=Not in use
Analogue input mode
Input maximum 0...2000
Ω
1
2000
Maximum analogue input value for
mA or resistance scaling
Input minimum
0...2000
Ω
1
0
Minimum analogue input value for
mA or resistance scaling
Table continues on the next page
1MRS757644 H
Basic functions
620 series
Technical Manual
129