4.3.4.12
Technical data
Table 508: HREFPDIF Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured current: f
n
±2
Hz
±1.5% of the set value or ±0.002 × I
n
Start time ,
Minimum
Typical
Maximum
I
Fault
= 2.0 × set
Operate value
I
Fault
= 10.0 × set
Operate val-
ue
16 ms
11 ms
21 ms
13 ms
23 ms
14 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<35 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
4.3.4.13
Technical revision history
Table 509: HREFPDIF Technical revision history
Technical revision
Change
B
Internal improvement.
C
Internal improvement.
4.3.5
High-impedance differential protection HIxPDIF
4.3.5.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
High-impedance differential pro-
tection for phase A
HIAPDIF
dHi_A>
87A
High-impedance differential pro-
tection for phase B
HIBPDIF
dHi_B>
87B
High-impedance differential pro-
tection for phase C
HICPDIF
dHi_C>
87C
1
Current before fault = 0.0, f
n
= 50 Hz, results based on statistical distribution of 1000 measure-
ments.
2
Includes the delay of the signal output contact.
Protection functions
1MRS757644 H
582
620 series
Technical Manual