Name
Type
Default
Description
I_A2
SIGNAL
0
Phase A secondary
current
I_B2
SIGNAL
0
Phase B secondary
current
I_C2
SIGNAL
0
Phase C secondary
current
BLOCK
BOOLEAN
0=False
Block
BLK_OPR_LS
BOOLEAN
0=False
Blocks operate out-
puts from biased
stage
BLK_OPR_HS
BOOLEAN
0=False
Blocks operate out-
puts from instantane-
ous stage
TAP_POS
INT8
0
Tap position indica-
tion
Table 485: TR2PTDF Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operate combined
OPR_LS
BOOLEAN
Operate from low set
OPR_HS
BOOLEAN
Operate from high set
BLKD2H
BOOLEAN
2nd harmonic restraint block
status
BLKD5H
BOOLEAN
5th harmonic restraint block
status
BLKDWAV
BOOLEAN
Waveform blocking status
4.3.2.8
Settings
Table 486: TR2PTDF Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
High operate value 500...3000
%Ir
10
1000
Instantaneous
stage setting
Low operate value
5...50
%Ir
1
20
Basic setting for
biased operation
Slope section 2
10...50
%
1
30
Slope of the second
line of the operat-
ing characteristics
End section 2
100...500
%Ir
1
150
Turn-point be-
tween the second
and the third line of
the operating char-
acteristics
Restraint mode
5=Waveform
6=2.h + waveform
8=5.h + waveform
9=2.h + 5.h + wav
9=2.h + 5.h + wav
Restraint mode
Table continues on the next page
1MRS757644 H
Protection functions
620 series
Technical Manual
553