Figure 208: Example of INTRPTEF operation in ”Transient EF” mode in the faulty
feeder
In the "Intermittent EF" mode the
OPERATE
output is activated when the following
conditions are fulfilled:
• the number of transients that have been detected exceeds the
Peak counter limit
setting
• the timer has reached the time set with the
Operate delay time
• and one additional transient is detected during the drop-off cycle
The
Reset delay time starts to elapse from each detected transient (peak). In case
there is no
OPERATE
activation, for example, the fault disappears momentarily
START
stays activated until the
Reset delay time elapses, that is, reset takes place
if time between transients is more than
Reset delay time. After
OPERATE
activation,
a fixed pulse length of 100 ms for
OPERATE
is given, whereas
START
is reset after
Reset delay time elapses
1MRS757644 H
Protection functions
620 series
Technical Manual
423