Table 687: UEXPDIS Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
External Los Det
Ena
0=Disable
1=Enable
1=Enable
Enable external ex-
citation loss detec-
tion
Voltage reversal
0=No
1=Yes
0=No
Rotate voltage sig-
nals by 180 degrees
Impedance Meas
mode
1=1Phase-to-earth
2=1Phase-to-phase
3=3Phase-to-earth
4=3Phase-to-phase
5=Pos sequence
5=Pos sequence
Select voltage and
currents for impe-
dance calculation
Phase Sel for Z Clc
1=A or AB
2=B or BC
3=C or CA
1=A or AB
Voltage phase se-
lection
Table 688: UEXPDIS Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
10
3000
Reset delay time
4.7.1.8
Monitored data
Table 689: UEXPDIS Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time / op-
erate time (in %)
Z_AMPL_A
FLOAT32
0.00...200.00
xZn
Impedance amplitude
phase A
Z_ANGLE_A
FLOAT32
-180.00...180.00
deg
Impedance angle phase
A
Z_AMPL_B
FLOAT32
0.00...200.00
xZn
Impedance amplitude
phase B
Z_ANGLE_B
FLOAT32
-180.00...180.00
deg
Impedance angle phase
B
Z_AMPL_C
FLOAT32
0.00...200.00
xZn
Impedance amplitude
phase C
Z_ANGLE_C
FLOAT32
-180.00...180.00
deg
Impedance angle phase
C
Z_AMPL_AB
FLOAT32
0.00...200.00
xZn
Phase-to-phase A-B im-
pedance amplitude
Z_ANGLE_AB
FLOAT32
-180.00...180.00
deg
Phase-to-phase A-B im-
pedance phase angle
Z_AMPL_BC
FLOAT32
0.00...200.00
xZn
Phase-to-phase B-C im-
pedance amplitude
Z_ANGLE_BC
FLOAT32
-180.00...180.00
deg
Phase-to-phase B-C im-
pedance phase angle
Z_AMPL_CA
FLOAT32
0.00...200.00
xZn
Phase-to-phase C-A im-
pedance amplitude
Table continues on the next page
1MRS757644 H
Protection functions
620 series
Technical Manual
727