Table 861: HZCCCSPVC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
10
20
Reset delay time
Measurement
mode
2=DFT
3=Peak-to-Peak
2=DFT
Selects used meas-
urement mode
6.4.9
Monitored data
Table 862: HZCCASPVC Monitored data
Name
Type
Values (Range)
Unit
Description
HZCCASPVC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Table 863: HZCCBSPVC Monitored data
Name
Type
Values (Range)
Unit
Description
HZCCBSPVC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Table 864: HZCCCSPVC Monitored data
Name
Type
Values (Range)
Unit
Description
HZCCCSPVC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
6.4.10
Technical data
Table 865: HZCCxSPVC Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the current measured: f
n
±2 Hz
±1.5 % of the set value or ±0.002 × I
n
Reset time
<40 ms
Reset ratio
Typically 0.96
Retardation time
<35 ms
Operate time accuracy in definite time mode
±1.0 % of the set value or ±20 ms
1MRS757644 H
Supervision functions
620 series
Technical Manual
897