Figure 454: The behavior of fault distance estimate in time
5.7.4.4
Alarm indication
SCEFRFLO contains an alarm output for the calculated fault distance. If the
calculated fault distance FLT_DISTANCE is between the settings
Low alarm Dis limit
and
High alarm Dis limit, the
ALARM
output is activated.
The
ALARM
output can be utilized, for example, in regions with waterways or other
places where knowledge of certain fault locations is of high importance.
Figure 455: An example of the ALARM output use
1MRS757644 H
Protection related functions
620 series
Technical Manual