4.5.10.6
Signals
Table 654: VVSPPAM Input signals
Name
Type
Default
Description
U_A_AB
SIGNAL
0
Phase-to-earth volt-
age A or phase-to-
phase voltage AB
U_B_BC
SIGNAL
0
Phase-to-earth volt-
age B or phase-to-
phase voltage BC
U_C_CA
SIGNAL
0
Phase-to-earth volt-
age C or phase-to-
phase voltage CA
BLOCK
BOOLEAN
0=False
Block signal for acti-
vating the blocking
mode
Table 655: VVSPPAM Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operate
INT_BLKD
BOOLEAN
Protection function internally
blocked
4.5.10.7
Settings
Table 656: VVSPPAM Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value
2.0...30.0
deg
0.1
6.0
Start value for vec-
tor shift
Table 657: VVSPPAM Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Over Volt Blk value
0.40...1.50
xUn
0.01
1.20
Voltage above
which function
will be internally
blocked
Under Volt Blk val-
ue
0.15...1.00
xUn
0.01
0.80
Voltage below
which function
will be internally
blocked
Table 658: VVSPPAM Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
1MRS757644 H
Protection functions
620 series
Technical Manual
699