PRES_ALM
BOOLEAN
Pressure below alarm level
PRES_LO
BOOLEAN
Pressure below lockout level
OPENPOS
BOOLEAN
CB is in open position
INVALIDPOS
BOOLEAN
CB is in invalid position (not
positively open or closed)
CLOSEPOS
BOOLEAN
CB is in closed position
7.1.7
Settings
Table 883: SSCBR Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Acc stop current
5.00...500.00
A
0.01
10.00
RMS current set-
ting below which
engy acm stops
Open alarm time
0...200
ms
1
40
Alarm level setting
for open travel time
in ms
Close alarm time
0...200
ms
1
40
Alarm level Setting
for close travel
time in ms
Spring charge time 0...60000
ms
10
15000
Setting of alarm
for spring charging
time of CB in ms
Alarm Op number
0...99999
1
200
Alarm limit for
number of opera-
tions
Lockout Op num-
ber
0...99999
1
300
Lock out limit for
number of opera-
tions
Current exponent
0.00...2.00
0.01
2.00
Current exponent
setting for energy
calculation
Difference Cor time -10...10
ms
1
5
Corr. factor for
time dif in aux.
and main contacts
open time
Alm Acc currents
Pwr
0.00...20000.00
0.01
2500.00
Setting of alarm
level for accumula-
ted currents power
LO Acc currents
Pwr
0.00...20000.00
0.01
2500.00
Lockout limit set-
ting for accumula-
ted currents power
Directional Coef
-3.00...-0.50
0.01
-1.50
Directional coeffi-
cient for CB life cal-
culation
Initial CB Rmn life
0...99999
1
5000
Initial value for the
CB remaining life
Rated Op current
100.00...5000.00
A
0.01
1000.00
Rated operating
current of the
breaker
Rated fault current 500.00...75000.00
A
0.01
5000.00
Rated fault current
of the breaker
Op number rated
1...99999
1
10000
Number of opera-
tions possible at
rated current
Table continues on the next page