Table 33: Optional operation modes for setting group selection
SG operation mode
Description
Operator (Default)
Setting group can be changed with the setting Settings > Setting
group > Active group.
Value of the
SG_LOGIC_SEL
output is FALSE.
Logic mode 1
Setting group can be changed with binary inputs
(
BI_SG_2...BI_SG_6
). The highest
TRUE
binary input defines the
active setting group.
Value of the
SG_LOGIC_SEL
output is TRUE.
Logic mode 2
Setting group can be changed with binary inputs where
BI_SG_4
is
used for selecting setting groups 1-3 or 4-6.
When binary input
BI_SG_4
is
FALSE
, setting groups 1-3 are selec-
ted with binary inputs
BI_SG_2
and
BI_SG_3
. When binary input
BI_SG_4
is
TRUE
, setting groups 4-6 are selected with binary inputs
BI_SG_5
and
BI_SG_6
.
Value of the
SG_LOGIC_SEL
output is TRUE.
The setting group (SG) is changed whenever switching the
SG operation
mode setting from "Operator" to either "Logic mode 1" or "Logic mode
2." Thus, it is recommended to select the preferred operation mode at
the time of installation and commissioning and not change it throughout
the protection relay's service. Changing the
SG operation mode setting
from "Logic mode 1" to "Logic mode 2" or from "Logic mode 2" to "Logic
mode 1" does not affect the setting group (SG).
For example, six setting groups can be controlled with three binary inputs. The
SG
operation mode is set to “Logic mode 2” and inputs
BI_SG_2
and
BI_SG_5
are
connected together the same way as inputs
BI_SG_3
and
BI_SG_6
.
Table 34: SG operation mode = “Logic mode 1”
Input
BI_SG_2
BI_SG_3
BI_SG_4
BI_SG_5
BI_SG_6
Active group
FALSE
FALSE
FALSE
FALSE
FALSE
1
TRUE
FALSE
FALSE
FALSE
FALSE
2
any
TRUE
FALSE
FALSE
FALSE
3
any
any
TRUE
FALSE
FALSE
4
any
any
any
TRUE
FALSE
5
any
any
any
any
TRUE
6
Table 35: SG operation mode = “Logic mode 2”
Input
BI_SG_2
BI_SG_3
BI_SG_4
BI_SG_5
BI_SG_6
Active group
FALSE
FALSE
FALSE
any
any
1
TRUE
FALSE
FALSE
any
any
2
Table continues on the next page
1MRS757644 H
Basic functions
620 series
Technical Manual
93