Table 519: HIBPDIF Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operate value
1.0...200.0
%In
1.0
5.0
Operate value, per-
centage of the
nominal current
Minimum operate
time
20...300000
ms
10
20
Minimum operate
time
Table 520: HIBPDIF Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Table 521: HIBPDIF Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
10
20
Reset delay time
Table 522: HICPDIF Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operate value
1.0...200.0
%In
1.0
5.0
Operate value, per-
centage of the
nominal current
Minimum operate
time
20...300000
ms
10
20
Minimum operate
time
Table 523: HICPDIF Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Table 524: HICPDIF Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
10
20
Reset delay time
4.3.5.9
Monitored data
Table 525: HIAPDIF Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time / op-
erate time
HIAPDIF
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
1MRS757644 H
Protection functions
620 series
Technical Manual