Parameter
Values (Range)
Unit
Step
Default
Description
Curve parameter A 0.0086...120.0000
1
28.2000
Parameter A for
customer program-
mable curve
Curve parameter B 0.0000...0.7120
1
0.1217
Parameter B for
customer program-
mable curve
Curve parameter C 0.02...2.00
1
2.00
Parameter C for
customer program-
mable curve
Curve parameter D 0.46...30.00
1
29.10
Parameter D for
customer program-
mable curve
Curve parameter E 0.0...1.0
1
1.0
Parameter E for
customer program-
mable curve
Table 320: PHPVOC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Measurement
mode
1=RMS
2=DFT
3=Peak-to-Peak
2=DFT
Selects used meas-
urement mode
Control mode
1=Voltage control
2=Input control
3=Voltage and in-
put Ctl
4=No Volt depend-
ency
1=Voltage control
Type of control
Minimum operate
time
40...60000
ms
1
40
Minimum operate
time for IDMT
curves
Reset delay time
0...60000
ms
1
20
Reset delay time
4.1.5.8
Monitored data
Table 321: PHPVOC Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start
time / operate
time
EFF_ST_VAL_A
FLOAT32
0.00...50.00
xIn
Effective start
value for phase A
EFF_ST_VAL_B
FLOAT32
0.00...50.00
xIn
Effective start
value for phase B
Table continues on the next page
1MRS757644 H
Protection functions
620 series
Technical Manual